SHOCK RELAY
Description
Function :
Current Monitors are used to detect conditions of Overload , Underload, and other faults in an electrical system.
| Reliable Solid state Electronics Design. |
| The current limit can be set very easily, continuously & Precisely. |
| Built in LEDs for Trip Indication. |
| 3 ½ Digit, 7 segment LED display. |
| Continuously adjustable ON/OFF delays. |
| Adjustable Initial Bypass Delay. |
| Adjustable Trip Delay. |
| Adjustable Overcurrent & Undercurrent settings. |
| Multiple output contacts available. |
| 96 X 96 X 150 mm DIN enclosure suitable for Panel Door Mounting. |
Optional Features
| Facility of Remote Transmission. |
| Input | : AC Current (Iac), 50Hz |
|---|---|
| Range | : Max upto 10A direct or 0-1A or 0 -5A through external C.T.(Please Specify CT Ratio) |
| Output | : 1) 1 C/O relay Contact (1NO+1NC) per Set Point, rated for 5A at 240VAC on resistive load 2) 4-20 mA Output Proportional to Input Range (optional) |
| Display | : 3 ½ Digit, 7 Segment LED display |
| User Interface | : Through keys |
| LED Indication | : 1) Overcurrent 2) Undercurrent |
| Setting Ranges | : 1) Overcurrent (High Trip Point) : 40 to 200 % Adjustable 2) Undercurrent (Low Trip Point) : 05 to 30% Adjustable |
| Delay | : 1) Initial Bypass Delay: 0.2 to 20 sec (Adjustable) 2) Trip Delay: 0.2 to 20 sec (Adjustable) |
| Reset | : Auto / Manual (Please Specify) |
| Enclosure | : 96 X 96 X 150mm, DIN rail mounting, Suitable for Panel Door Mounting |
Reliable & Solid state electronics design finds its application in
Machine Tools.
Material Handling Systems.
Cranes.
Hoists.